4.9 stars · 197 reviews · 24hr reports
Card reading 10 per cent, the share of a storey that decides whether a part gets its own building class. An office at 8 per cent of a factory leaves the whole building Class 8; at 12 per cent that office becomes Class 5.
Building Inspections
Building classification · NCC and the Building Act
Your building has a class, and since 1 July 2026 one of those classes carries a duty with a penalty of up to half a million dollars.

The National Construction Code sorts every building into one of ten classes by the purpose it was built for. Most people never learn theirs. Then a new section of the Building Act arrived that switches on only if a building is Class 2, and suddenly the label matters. This sets out the ten classes, the rule that decides them, the 10 per cent exemption that catches people out, and where the regulator's plain-English summary and the Act itself do not quite line up.

Published: 18 August 2026
Where: Australia wide, with Victorian law noted
Read time: ~11 min
Every figure on this page was drawn by Site Inspections from the rules themselves. No diagram, chart or table has been copied or adapted from the Building and Plumbing Commission or the Australian Building Codes Board, because both reserve their artwork. Rules and facts carry no copyright; the way a regulator draws them does.
Key facts
Classes in the Code
10
several carry sub-classes, so there are more labels than numbers
What decides your class
Purpose
not size, not appearance, not what the sign on the door says
The exemption threshold
10%
of the floor area of a storey. Below it, the minor use takes the major class
Maximum penalty, s 40A
2,500 units
for a body corporate. About $522,750 from 1 July 2026
Key takeaways
A building's class is set by the purpose it is designed, constructed or adapted for. A house is Class 1a. Apartments are Class 2. A garage or shed is Class 10a.
One building can hold several classes at once, and each part is classified separately. The rules that apply to your apartment are not the rules that apply to the carpark under it.
The 10 per cent rule. Where a minor use takes up less than 10 per cent of a storey's floor area it takes the major classification. The Code's own example: an office at 8 per cent of a factory leaves the whole building Class 8. At 12 per cent, that office becomes Class 5.
Since 1 July 2026, section 40A of the Victorian Building Act requires the developer of a residential apartment building to notify the regulator before applying for an occupancy permit. It only bites if the building is Class 2. The penalty runs to 2,500 penalty units for a company.
That duty is a window, not a deadline. The Act sets a period that opens 12 months before the occupancy permit application and closes six months before it. The regulator's summary says "at least 6 months prior", which does not convey the opening.

01What a building class actually is

One rule decides it, and it is not the one most people assume.

The National Construction Code does not sort buildings by size, or height, or what they are made of. It sorts them by what they are for. In the Code's own words, it "groups buildings and structures by the purpose for which they are designed, constructed or adapted to be used".

That single idea does more work than it looks like. It means a building's class can change without a brick moving, if the use changes. It means two buildings that look identical from the street can carry different classes. And it means the question is never "what does this building look like", it is "what is this part of it for".

The classification then decides which technical requirements apply. Fire separation, exits, sanitary facilities, energy efficiency, access: the Code sets different requirements for different classes because the risks are different. A warehouse and a childcare centre do not need the same things, and the class is how the Code knows which is which.

There are ten classes, numbered 1 to 10, and several carry sub-classes marked by a letter. Class 1a is a house. Class 1b is a small guest house. Class 10a is a garage or shed. That lettering is where most of the detail lives.

02The ten classes

Grouped by what they are for, which is easier to remember than the numbers.

The numbering is not intuitive, and there is no point pretending otherwise. Class 7a is a carpark and Class 7b is a warehouse. Class 9b covers both a primary school and a night club. The fastest way to hold it is to stop reading it as a sequence and start reading it as four families.

Figure 1
The ten classes, grouped by what they are for.

Tap any class for the full definition and the rules that catch people out.

Places people live
Places people work
Places the public gathers
Nobody lives in these
Source: Building and Plumbing Commission, "Building classes" (16 July 2026), and NCC 2022 Volume One Part A6. The grouping into four families is ours, drawn to make the list easier to hold in your head. Icons and diagram drawn by Site Inspections; no regulator artwork is reproduced or adapted.

A few of those deserve expanding, because they are the ones people get wrong about their own property.

Class 1a is the one most readers live in. A detached house, or one of a group of attached dwellings separated by a fire-resisting wall, which is what a terrace or a townhouse is. Class 1b is a boarding house, guest house or hostel with not more than 12 occupants and a floor area not exceeding 300 square metres, or four or more single dwellings on one allotment used for short-term holiday accommodation.

Class 2 is apartments: a building containing two or more sole-occupancy units, each treated as a separate dwelling. This is the class that section 40A turns on, and it is covered in full below.

Class 10 is everything nobody lives in. 10a is a private garage, carport or shed. 10b is a structure rather than a building: a fence, a mast, an antenna, a retaining wall, a free-standing wall or a swimming pool. 10c is a private bushfire shelter. If you have ever wondered why a retaining wall or a pool fence attracts building requirements at all, this is why. They are classified structures.

03The edge cases that catch people out

Five rules that are not obvious from the class list, and change the answer.

Worth knowing before you argue about your own building
A Class 1 dwelling cannot sit above or below another dwelling or class. The one exception is a private garage. So a house with a flat above it is not two Class 1 dwellings; the arrangement itself changes the classification.
There can be only one Class 4 dwelling in a building. Class 4 is the caretaker's flat above the shop. If there are two of them, it is not Class 4 any more.
A medical clinic is Class 5, until the treatment causes unconsciousness. Where patient treatment causes unconsciousness or temporary ambulatory deficiency, it becomes Class 9a, which is health care. Day surgery is a different building class from a GP practice.
A service station is Class 6, but a panel beater is not. The Code is explicit that the expression is not intended to cover buildings used solely for panel beating, auto electrical work, muffler replacement, tyre replacement and the like. Those are workshops, and they sit elsewhere.
Class 9c residential care turns on a 10 per cent threshold of residents who need care. Below that, an aged care building may not be 9c at all.

None of this is trivia. Each of those rules moves a building into a different set of technical requirements, and requirements are what a defect is measured against. An owner who does not know their class is arguing about compliance without knowing which rules they are arguing under.

04One building can hold several classes at once

Each part is classified separately, and that is the rule most people have never heard.

A building is not given a single label at the front door. The Code requires that "each part of a building must be classified according to its purpose and comply with all the appropriate requirements for its classification". A mixed-use block is not a Class 2 building with some shops in it. It is a Class 2 part, a Class 6 part, a Class 5 part and a Class 7a part, each carrying its own requirements.

Figure 2
One building can hold four classifications at once.
2 Apartments, levels 2 to 6 Two or more sole-occupancy units, each a separate home This is the part that triggers section 40A 5 Offices, level 1 Professional or commercial use 6 Shops, ground floor Goods or services sold directly to the public 7a Carpark, basement A storage class, not a residential one "Each part of a building must be classified according to its purpose and comply with all the appropriate requirements for its classification." NCC 2022, A6G1(2) So the rules that apply to your apartment are not the rules that apply to the carpark beneath it, or the shop at the front. A plant room takes the class of the part it serves. An occupiable outdoor area takes the class it is attached to. Illustrative arrangement drawn by Site Inspections. Not a specific building.
Source: NCC 2022 Volume One, Part A6, A6G1(2), (3) and (4). Arrangement of floors is illustrative and chosen by us to show the rule; it is not a real building and no regulator figure is reproduced.

Two more allocation rules follow from the same idea and both are useful. A room containing a mechanical, thermal or electrical facility that serves the building takes the classification of the major part or principal use, rather than being classified on its own. And unless another classification is more suitable, an occupiable outdoor area takes the class of the part it is associated with. A rooftop terrace attached to apartments is not a separate thing; it goes with the apartments.

Where it genuinely is not clear, the Code hands the decision to the appropriate authority, which weighs what the building most closely resembles, the likely fire load, and the likely consequences of the risks. They will also look at relevant court decisions and determinations, and at any guidance the State or Territory has issued. In other words, classification is a judgement, and it is a judgement someone else makes about your building.

05The 10 per cent rule

The exemption that decides whether a small part of a building gets its own classification.

If every part had to be classified separately with no tolerance, a factory with a desk in the corner would be two buildings. So the Code carries an exemption. Where a part has been designed, constructed or adapted for a different purpose and is less than 10 per cent of the floor area of the storey it is on, that part takes the major classification instead of its own.

The Code supplies its own worked example, and it is worth seeing to scale.

Figure 3
The 10 per cent rule. Four percentage points change which code applies.
SINGLE STOREY FACTORY, OFFICE AT 8% office 8% CLASS 8 The whole building, office included. One classification. Under 10%, so the minor use takes the major classification. SAME FACTORY, OFFICE AT 12% office 12% CLASS 8 The remainder of the building. + CLASS 5 Over 10%, so the office must be classified separately. "If a single storey factory has an office that takes up 8% of the whole storey's floor area, the entire building (including the office) can be classified as being Class 8. However, if that office area takes up 12% of the storey's floor area, that area must be classified as Class 5, and the remainder of the building as Class 8." NCC 2022 Volume One, Part A6, explanatory material to A6G1 Exemption (1) The exemption does not apply where the minor use is a laboratory, a Class 9b early childhood centre, or a Class 2, 3 or 4 part.
Source: NCC 2022 Volume One, Part A6, A6G1 Exemption (1) and its explanatory material. The worked example is the NCC's own. Plans drawn by Site Inspections to illustrate the arithmetic; no NCC figure is reproduced or adapted.

Four percentage points is the whole difference. At 8 per cent the office is simply part of a Class 8 factory. At 12 per cent it is a Class 5 office that happens to be inside one, with Class 5 requirements attached to it.

There is a limit on the exemption and it matters more than the exemption does. It does not apply where the minor use is a laboratory, a Class 9b early childhood centre, or a Class 2, 3 or 4 part of a building. So a small childcare room inside a larger building does not get absorbed by the major classification no matter how small it is, and neither does a single apartment inside a commercial building. The Code has decided those uses carry risk that a percentage cannot wash out.

Why a percentage is worth arguing about

The Code notes that where a storey has a very large floor area, the 10 per cent concession is also large. Ten per cent of a big warehouse floor is a substantial room. The exemption is not a small-print allowance for a cupboard; on a large building it can absorb a genuinely sizeable space into a classification that carries lighter requirements than the space would attract on its own.

06Why the label suddenly matters: section 40A

A duty that arrived on 1 July 2026 and is switched on entirely by classification.

Until recently a homeowner could go a whole build without learning their building class. Then section 40A was inserted into the Victorian Building Act 1993, and a new obligation arrived that applies to some buildings and not others, on the basis of the class.

Section 40A(1), in full

"The developer of a residential apartment building must ensure notice of intention to apply for an occupancy permit is given to the Authority in accordance with subsection (2) before the end of the applicable period in respect of the residential apartment building."

"Penalty: 500 penalty units, in the case of a natural person; 2500 penalty units, in the case of a body corporate."

A Victorian penalty unit was fixed at $209.10 for the financial year commencing 1 July 2026. On that figure, and the multiplication is ours rather than the Act's, the maximum is about $104,550 for an individual and $522,750 for a company. The regulator's own guidance page describes the duty without mentioning the penalty at all.

Whether it applies to a given building is a classification question, and the Act defines it tightly.

Figure 4
Section 40A: three things must all be true.
1 A Class 2 building, or part of one AND 2 Rise in storeys of more than 3 AND 3 Contains 2 or more homes The developer must give the regulator notice of intention to apply for an occupancy permit. Penalty: up to 2,500 penalty units for a body corporate Regulations may exclude some Class 2 buildings or parts. Those exclusions were not examined here. Victorian scheme. Section 40A, Building Act 1993, in force from 1 July 2026.
Source: Building Act 1993 (Vic), authorised version 149 as at 30 July 2026, section 3(1) definition of residential apartment building and section 40A(1). Diagram by Site Inspections.

The definition in section 3(1) is a "class 2 building within the meaning of the Building Code of Australia with a rise in storeys of more than 3", or part of one, "that contains 2 or more homes", excluding anything the regulations carve out. The regulator's guidance renders the height test as "a rise in storeys of 4 or more", which is the same thing said differently. It does not mention the two-or-more-homes limb.

The part that is easy to get wrong

The guidance page says to notify "at least 6 months prior to making an application for an Occupancy Permit". Read plainly, that sounds like a deadline with an open runway behind it: any time up to six months out is fine, and earlier is safer.

The Act does not say that. It defines an applicable period with a start and an end.

Figure 5
It is a window, not a deadline. It closes six months out.
NORMAL BUILD too early THE WINDOW too late 12 monthsbefore 6 monthsbefore occupancy permitapplication BUILD COMPLETED WITHIN SIX MONTHS too early THE WINDOW 6 months before 30 days before "the period commencing 12 months before the occupancy permit application date and ending 6 months before the occupancy permit application date" Building Act 1993 (Vic), s 40A(5), definition of applicable period
Source: Building Act 1993 (Vic), authorised version 149 as at 30 July 2026, section 40A(5). The regulator's guidance page summarises this as "at least 6 months prior", which does not convey that the period also has an opening. Diagram by Site Inspections from the section's own wording.

For a normal build the period commences 12 months before the occupancy permit application date and ends six months before it. For work to be completed within six months, it commences six months before and ends 30 days before. On the section's own wording the window shuts, and it also opens. Notifying eighteen months out is not obviously compliance with a period that commences at twelve.

We are not saying the regulator's page is wrong. It is plain-English guidance and it is entitled to summarise a definition that runs to two limbs. But guidance is not the instrument, and anyone relying on this should read section 40A(5) rather than the summary of it. That is a general principle worth more than this one section: the summary tells you a rule exists, the instrument tells you what it says.

One more limb sits underneath. If notice has already been given and the developer becomes aware of a change in circumstances affecting the application date, a further notice must be given within five business days. And according to the regulator, the requirement reaches building permits issued both before and after 1 July 2026, so projects already under way are caught.

If you are buying off the plan or taking handover in an apartment building, this is worth knowing for a reason that has nothing to do with compliance paperwork. A regulator that is told six months ahead which apartment buildings are approaching an occupancy permit is a regulator in a position to look at them.

07What to do with this

Four practical uses, and one that saves an argument.

Figure 6
Which volume of the Code governs you.
Volume Two Class 1 and Class 10 Houses, townhouses, garages, sheds, fences, pools Volume One Class 2 to Class 9 Apartments, offices, shops, warehouses, schools, hospitals Plumbing and drainage sit in Volume Three. Victoria adopts the NCC with state variations, and the edition that governs a build follows the permit date. This describes NCC 2022. NCC 2025 is published; check which edition your permit was issued under.
Source: NCC 2022 Volume One, Part A6, and the BPC building regulatory framework page. Diagram by Site Inspections.
Four things worth doing
Find your class on the permit. The building permit states the classification. It is not a detail buried in an engineer's report; it is on the face of the document, and it decides which requirements your build had to meet.
Check the edition too. The Code that governs a build follows the permit date, not today's date. This article describes NCC 2022. NCC 2025 is published. A defect is assessed against the edition your permit was issued under.
If your building is mixed use, ask which part you are in. Your apartment and the carpark beneath it are different classifications carrying different requirements. Complaints about one are not answered by the rules for the other.
If you are in a Class 2 building of more than three storeys, section 40A now applies to your developer. Ask whether the notice has been given, and when.

The reason any of this matters to an owner is narrow and specific. A defect is not an opinion about workmanship. It is a departure from a requirement, and the requirements that apply to your building are chosen by its class. Argue about a defect without knowing the class and you are arguing about the wrong rulebook.

That is the part we do. Site Inspections documents defects against the requirement they actually engage, for the class the building actually is, in the format an insurer, a tribunal or a rectifying builder can act on.

Get a defects report that names the requirement
We don't just do inspections. We investigate.
Request a defects report
Every job is quoted. Or contact us to talk it through first.

08Sources

Every quotation on this page comes from one of these, with the section or clause named beside it.

1.
Building Act 1993 (Vic), Authorised Version No. 149, as at 30 July 2026
Section 40A, notice of intention to apply for an occupancy permit, inserted by Act No. 17/2025 s 94, including the penalty and the section 40A(5) definition of applicable period. Section 3(1) definition of residential apartment building. legislation.vic.gov.au
2.
National Construction Code 2022, Volume One, Part A6 Building classification
Australian Building Codes Board. A6G1 and its explanatory material, including Exemption (1), the 10 per cent rule and the worked factory example. Paraphrased with short quotations; no ABCB figure is reproduced or adapted. ncc.abcb.gov.au
3.
Building and Plumbing Commission, "Building classes"
Page dated 16 July 2026. The Victorian regulator's plain-English statement of the ten classes and the edge cases. Paraphrased with short quotations for review and reporting; no BPC material is reproduced or adapted. bpc.vic.gov.au
4.
Building and Plumbing Commission, "Notify BPC about a residential apartment building"
Page dated 23 July 2026. The source for the statement that the requirement applies to permits issued before and after 1 July 2026, which is attributed to the regulator and was not located in the Act text. bpc.vic.gov.au
5.
Victoria Government Gazette No. S 234, 5 May 2026
Notice under section 6 of the Monetary Units Act 2004 fixing the value of a penalty unit at $209.10 for the financial year commencing 1 July 2026. The conversion of penalty units to dollars in this article is our arithmetic, and the unit value is re-fixed every financial year.

Every figure on this page was drawn by Site Inspections from the rules described. No diagram, chart, table or image from the Australian Building Codes Board or the Building and Plumbing Commission has been reproduced, adapted, redrawn or traced. Both bodies reserve their material, and the BPC expressly names diagrams. The classifications themselves are rules and carry no copyright; the way a regulator chooses to present them does.

General information, not legal advice. Building classification depends on the facts of a particular building and is ultimately determined by the appropriate authority. This article describes NCC 2022; NCC 2025 is published, and the edition that governs a build follows the permit date. Section 40A of the Building Act 1993 is Victorian law; Site Inspections works Australia wide and other states have their own requirements. Penalty unit values are re-fixed every financial year and the dollar conversions here are our arithmetic based on the value gazetted for the year commencing 1 July 2026. Regulations may exclude some buildings from the section 40A definition and those exclusions were not examined here. Refer to the sources above and seek advice about your own circumstances.

Our Blog

YOUR GO-TO RESOURCE HUB

Whether you’re on the hunt or have already settled in, we’ll arm you with the know-how and confidence to keep your home safe and compliant. With our guidance, you can make informed decisions and steer clear of common pitfalls.

SEE ALL